Installation
OperatingManualPNOZmB0
1002660EN03
14
5 Installation
5.1 Installbaseunitwithoutexpansionmodule
Makesurethattheterminatorsareinsertedonthetopleftandrightoftheunit.
IM0
IM1
IM2 I6
I5
I4IM3 I7
I8
I9
I10 I14
I13
I12I11 I15
X3
X1
X4
X2
PNOZ mm0.1p
T0
T1
T2 O2
O1
O0T3 O3
IM16
IM17
IM18 0 V
A2
A1IM19 24 V
M20
M21
M22 M23
5.2 Controlcabinetinstallation
}
TheunitshouldbeinstalledinacontrolcabinetwithaprotectiontypeofatleastIP54.
}
Fitthesafetysystemtoahorizontalmountingrail.Theventingslotsmustfaceupward
anddownward.Othermountingpositionscoulddamagethesafetysystem.
}
Usethelockingelementsontherearoftheunittoattachittoamountingrail.
}
Inenvironmentsexposedtoheavyvibration,theunitshouldbesecuredusingafixing
element(e.g.retainingbracketorendangle).
}
Openthelockingslidebeforeliftingtheunitfromthemountingrail.
}
TocomplywithEMCrequirements,themountingrailmusthavealowimpedancecon
nectiontothecontrolcabinethousing.
CAUTION!
Damageduetoelectrostaticdischarge!
Electrostaticdischargecandamagecomponents.Ensureagainstdischarge
beforetouchingtheproduct,e.g.bytouchinganearthed,conductivesur
faceorbywearinganearthedarmband.