6.1 General wiring guidelines
6 Wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-2
Base module with cage clamp terminals:
Insert the screwdriver [4] into the square hole [1].
Insert the stripped cable into the round fixing hole [2], as far as it
will go [5].
Pull out the screwdriver [6].
Check that the cable is firmly seated.
][Modulverdrahtung el Sys A + B
Please note:
The minimum cable cross section for field connection terminals on the
base modules is 0.14 mm
2
(AWG26)
The maximum cable cross section for field connection terminals is:
Digital inputs: 1.5 mm
2
(AWG16)
Digital outputs: 2.0 mm
2
(AWG14)
Inputs/outputs on the counter modules: 1.5 mm
2
(AWG16)
Analogue inputs/outputs: 1.5 mm
2
(AWG16)
Communication cables: 1.5 mm
2
(AWG16)
Test pulse outputs: 1.5 mm
2
(AWG16)
Power supply: 2.5 mm
2
(AWG12)
Functional earth: 2.5 mm
2
(AWG12)
2111