6.2 Terminal configuration
6 Wiring
6.2Terminal configuration6200Terminal configuration6-][Klemmenbelegung XB
Base module Terminal configuration
Screw terminals:
PSSu BP 2/16S
PSSu BP 2/16S-T
Cage clamp terminals:
PSSu BP 2/16C
PSSu BP 2/16C-T
Without C-rail:
11-21: 0 V periphery supply
(11-21 linked internally)
12-22: 0 V periphery supply
(12-22 linked within the base module)
13-23: +24 V periphery supply
(13-23 linked within the base module)
14-24: +24 V periphery supply
(14-24 linked internally)
31-41-32-42-33-43-34-44 not con-
nected
Screw terminals:
PSSu BP-C 2/16S
PSSu BP-C 2/16S-T
Cage clamp terminals:
PSSu BP-C 2/16C
PSSu BP-C 2/16C-T
With C-rail:
11-21: 0 V periphery supply
(11-21 linked internally)
12-22: 0 V periphery supply
(12-22 linked within the base module)
13-23-33-43: C-rail supply
(13-23-33-43 linked within the base
module)
14-24: +24 V periphery supply
(14-24 linked internally)
31-41-32-42-34-44 not connected