Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
6-11
6.3 Connection examples
6 Commissioning
6.3.1.2 Example 2: Connection of 5 base units
Example 2: Connection of 5 base units6-Anschlussbeispiel_Verbindungsmodul_Reihenschalitung_5_Basisgeräte_Text
The reaction times are calculated in the same way as application exam-
ple 1. After pressing S1 on Base 1, the semiconductor outputs switch
after the following reaction times t
SUM
:
O0 on Base 2: 69 ms
O1 on Base 3: 104 ms
O0 on Base 4: 139 ms
O0 on Base 5: 104 ms
_Dummy-Vorlage
I3
I6
Base 1 Base 2
Base 3
S1
K3
Base 4
Base 5
I4 I6
K2
O0
O1
K4
O0
K5
O0
Comentários a estes Manuais