Installation
OperatingManualPNOZmESCANopen
1002699EN03
13
5 Installation
5.1 Generalinstallationguidelines
}
Theunitshouldbeinstalledinasinglemountingareawithaprotectiontypeofatleast
IP54.
}
Fitthesafetysystemtoahorizontalmountingrail.Theventingslotsmustfaceupwards
anddownwards.Othermountingpositionscoulddestroythesafetysystem.
}
Usethelockingslideontherearoftheunittoattachittoamountingrail.
}
Inenvironmentsexposedtoheavyvibration,theunitshouldbesecuredusingafixing
element(e.g.retainingbracketorendangle).
}
Openthelockingslidebeforeliftingtheunitfromthemountingrail.
}
TocomplywithEMCrequirements,themountingrailmusthavealowimpedancecon
nectiontothecontrolcabinethousing.
}
TheambienttemperatureofthePNOZmultiunitsinthecontrolcabinetmustnotexceed
thefigurestatedinthetechnicaldetails,otherwiseairconditioningwillberequired.
CAUTION!
Damageduetoelectrostaticdischarge!
Electrostaticdischargecandamagecomponents.Ensureagainstdischarge
beforetouchingtheproduct,e.g.bytouchinganearthed,conductivesur
faceorbywearinganearthedarmband.
5.1.1 Dimensions
101,4 (4,11)
115,0 (4,53)
22,5
(0,88“)
Vista de página 12