7.1 Messages
7 Operation
77000OperationOperation7-7.1Messages7100Messages7-][BA_Betrieb Meldungen ST-Bus
All errors and faults detected by the electronic modules on a PSSu are
signalled to the head module and entered in the head module's error
stack.
][BA_Betrieb Tabelle Meldungen ST
(
1
) There are two levels of overtemperature.
Too warm:
If a module's temperature exceeds a theshold value, the module
sends a warning to the head module. If the temperature drops back
below the threshold value, the module sends an all-clear.
Too hot:
If a module's temperature exceeds a further theshold value, the mod-
ule sends an error message to the head module.
Module error Explanation Remedy
Start-up error Error as the PSSu system starts up Change faulty module.
Configuration Error Incorrect module type configured. The configured hardware registry does
not match the actual hardware regis-
try.
ST communication error Error during ST communication Change faulty module.
Bus termination error There is no terminating plate or there is
a bad contact with the module bus.
Install a terminating plate with inte-
grated end bracket or insert the base
modules together correctly.
Temperature error: Too warm (
1
) Ambient temperature too high:
Error stack entry
Ensure there is sufficient ventilation in
the control cabinet or prevent over-
load.
Temperature error: Too hot (
1
) Ambient temperature too high:
Module reset
Ensure there is sufficient ventilation in
the control cabinet or prevent over-
load.
Overvoltage error A system voltage or infeed is too high. Stabilise the supply or change the
faulty supply voltage module.
Undervoltage error A system voltage or infeed is too low. Stabilise the supply or change the
faulty supply voltage module.