7.2 Display elements
7 Operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
7-2
7.2Display elements7200Display elements7-Anzeige Legende 3x
Legend:
7.2.1 Display elements for system diagnostics
Display elements for system diagnostics7-][BA_Anzeige System
The module has LEDs to display various PSSu states (“Usb” LED and
“Dev” LED).
(*
1
) An error on the module bus (flashing red LED) may be due to one of
the following reasons, which are stored in the error stack:
1. The head module cannot determine the registered hardware. Possible
causes:
Module bus is incomplete
Terminating resistor is missing.
A module is defective
A module does not have valid software.
Invalid hardware registry
Too many modules
LED on
LED flashes
LED off
LED Key
Description Colour Status
Usb - - - No data is being
transmitted via
the USB port
Green Data is being
transmitted via
the USB port
Dev - - - PSSu system
error, no start-
up
Green PSSu running
without error
Red Error in the
head module
Red Error on the
module bus (*
1
)