6.1 Wiring
6 Commissioning
66000CommissioningCommissioning6-6.1Wiring6100Wiring6-
6.1.1 General wiring guidelines
General wiring guidelin es6-Verdrahtung_multi_Modul
The wiring is defined in the circuit diagram of the PNOZmulti Configura-
tor.
Note:
Information given in the "Technical details" must be followed.
Verdrahtung_Montageschiene mit Schutzerde verbinden
Always connect the mounting rail to the protective earth via an earth-
ing terminal. This will be used to dissipate hazardous voltages in the
case of a fault.
Verdrahtung_Netzteil_sichere_Trennung
The power supply must meet the regulations for extra low voltages
with safe separation.
Verdrahtung_multi_Achtung_Kabel_spannungsl_ziehen_Modul
Verdrahtung_multi_Feldbus_Hinweis Nutzerorg_CANopen
6.1.2 Connecting the supply voltage
Connecting the supply voltage6-Verdrahtung_multi_Feldbus_Versorgungsspannung_Mini
Connect the supply voltage to the fieldbus module:
Terminal 24 V: + 24 V DC
Terminal 0 V: 0 V
CAUTION!
Only connect and disconnect the expansion module when the
supply voltage is switched off.
NOTICE
When installing, you must refer to the guidelines published by
the CANopen User Group (CiA).