5.4 Cable specification
Signal Cable specification
Data+ / Data–
(RS422+ / RS422–)
Min. 0.25 mm
2
, shielded stranded pair
Clock+ / Clock–
(RS422+ / RS422–)
A+ / A–
Min. 0.25 mm
2
, shielded stranded pair
B+ / B–
Supply
+24 VDC / 0 V
Min. 0.5 mm
2
, shielded stranded pair
The maximum cable length depends on the SSI clock frequency and cable
composition and should match the table below.
Please note that an additional delay time t
v
(Data+/Data–) of approx. 6 ns should be
calculated per metre of cable.
SSI clock frequency
[kHz]
810 750 570 360 220 120 100
Cable length [m]
Approx.
12.5
Approx.
25
Approx.
50
Approx.
100
Approx.
200
Approx.
400
Approx.
500