Pilz PSEN enc s2 eCAM Manual do Utilizador Página 86

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 93
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 85
Installation / Preparation for commissioning
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland
Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: [email protected]
37
English
5.9 Incremental interface
To output the absolute position, the standard version of the measuring system also
has an incremental interface in addition to the SSI interface.
The measuring system checks the outputs on this interface for external voltage
sources. The measuring system is shut down if voltages > 5.7 V arise. In this
state, the measuring system behaves as though it were not connected.
The interface is generally used for position feedback on motor control
applications.
NOTICE
Risk of damage to subsequent electronics due to
overvoltages caused by a missing earth reference
point!
If the earth reference point is missing entirely, e.g. 0 V
of the power supply is not connected, voltages equal
to the level of the supply voltage can occur at the
outputs of this interface.
A
n earth reference point must be guaranteed to be
present at all times.
5.9.1 Signal characteristic of the incremental interface
A corresponding number of pulses is output while completing a revolution. To
evaluate the count direction, a 2nd signal sequence with 90° phase offset is output for
the controller.
On the standard version, the incremental resolution of the measuring system is 4096
pulses / revolution. There is no zero pulse.
Vista de página 85
1 2 ... 81 82 83 84 85 86 87 88 89 90 91 92 93

Comentários a estes Manuais

Sem comentários